Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Click here for important information regarding CH operation
CH temperature control turned to MAX
Attach a temperature clamp to the flow pipe as indicated by the red arrow
CH temperature control turned to MAX
Attach a temperature clamp to the flow pipe as indicated by the red arrow
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the 4 minute pump purge to complete.
Allow the burner to ignite and the system to heat, the boiler should
maintain and/or shutdown at approximately 75°C.
Monitor the appliance temperature on the FGA.
Note:
To reduce the time for this test the heating load
can be reduced by temporarily turning off some radiators.
Allow the burner to ignite and the system to heat, the boiler should
maintain and/or shutdown at approximately 75°C.
Monitor the appliance temperature on the FGA.
Note:
To reduce the time for this test the heating load
can be reduced by temporarily turning off some radiators.