Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gain access to PCB (use Insulation Mat as required)
Disconnect plug from flow thermistor
Disconnect plug from flow thermistor
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
With the flow sensor disconnected the
appliance will immediately enter lockout.
This should make the appliance
run the pump constantly.
Measure the voltage between the brown
and blue wires at connector X4 on the PCB.
Mains voltage should be present.
appliance will immediately enter lockout.
This should make the appliance
run the pump constantly.
Measure the voltage between the brown
and blue wires at connector X4 on the PCB.
Mains voltage should be present.

Isolate as per TOPs P4
and refit as necessary