Set Appliance State:
Turn Hot Water Tap On
Observation:
Is the flow rate from the hot tap satisfactory?
Expected flow rate (approx) with tap fully open:
24kW & 28kW output: 10 litres / min
35kW & 39kW output: 14 litres / min
Information:
Minimum flow rate for boiler to operate for DHW is approx 2.5 litres/min. If the flow rate is above this but below the flow rate given above
(e.g. 7 litres / min) and you are confident the fault is not due to
the water supply then click "flow rate satisfactory".
Expected flow rate (approx) with tap fully open:
24kW & 28kW output: 10 litres / min
35kW & 39kW output: 14 litres / min
Information:
Minimum flow rate for boiler to operate for DHW is approx 2.5 litres/min. If the flow rate is above this but below the flow rate given above
(e.g. 7 litres / min) and you are confident the fault is not due to
the water supply then click "flow rate satisfactory".