Set Appliance State:
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Adjustment of the boilers maximum DHW
temperature is done via parameter P2.
Carry out instructions below to check the DHW temperature setting and adjust as necessary.
(parameters only accessible when appliance has completed self check)
1. Hold ⮠  until display alternates between P and 1. (approx. 2 secs)
2. Press + once so display alternates between P and 2.
3. Press ⮠ : display now shows maximum DHW temperature.
4. Press + or - buttons to change setting (default 55) then press ⮠  to confirm change.
Did the DHW temperature setting need adjusting?
temperature is done via parameter P2.
Carry out instructions below to check the DHW temperature setting and adjust as necessary.
(parameters only accessible when appliance has completed self check)
1. Hold ⮠  until display alternates between P and 1. (approx. 2 secs)
2. Press + once so display alternates between P and 2.
3. Press ⮠ : display now shows maximum DHW temperature.
4. Press + or - buttons to change setting (default 55) then press ⮠  to confirm change.
Did the DHW temperature setting need adjusting?