Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Disconnect plug (red leads) from flow sensor.
Measurement:
Measure the Resistance across the two sensor terminals, also measure the approximate temperature at the sensors location.
Note:
Ensure the sensor is correctly attached to the pipe.
The resistance will vary according the boiler temperature but should conform approximately to the table below at the appropriate temperature to ensure it is within range and in calibration.
Note:
Ensure the sensor is correctly attached to the pipe.
The resistance will vary according the boiler temperature but should conform approximately to the table below at the appropriate temperature to ensure it is within range and in calibration.
| Temperature °C | Resistance in kOhms | 20 | 10 |
| 30 | 6.6 |
| 40 | 5.8 |
| 50 | 3.1 |
| 60 | 2 |
| 70 | 1.5 |
| 80 | 1.1 |

Isolate as per TOPs P4
and refit as necessary