Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Allow fan to run and boiler to fire and allow system to reach a reasonable operating temperature.
Attach Temperature probes as indicated by the red arrows
Attach Temperature probes as indicated by the red arrows
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Using temp clamps measure the temperature of the flow and return pipes close to the primary heat exchanger.
Expected differential approx 11-20 °C.
Note:
For clarity the test is shown with the fan and burner removed but the test is carried out with these in place.
Click on your observation:
1. DIFFERENTIAL OK NOISE DUE TO EXCESSIVE HEAT
2.DIFFERENTIAL NOT OK NOISE LOCAL BOILING
3.DIFFERENTIAL OK SYSTEM NOISE
Expected differential approx 11-20 °C.
Note:
For clarity the test is shown with the fan and burner removed but the test is carried out with these in place.
Click on your observation:
1. DIFFERENTIAL OK NOISE DUE TO EXCESSIVE HEAT
2.DIFFERENTIAL NOT OK NOISE LOCAL BOILING
3.DIFFERENTIAL OK SYSTEM NOISE