Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove control box cover
No Demands
No Demands
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
With the connector still attached to the PCB. Measure the DC voltage between the Red wire (4th down from the top) on connector X22 and the neutral at the incoming mains terminal strip.
Expect either 5vdc or 0vdc
Expect either 5vdc or 0vdc

Isolate as per TOPs P4
and refit as necessary