Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to Resistance Set meter to measure resistance
Disconnect the wiring from the flue overheat stat

Measurement:

Measure resistance across the terminals of the flue overheat thermostat.
Note:
It may be necessary to remove the flue stat which is a bayonet fitting remember to check the integrity of the seal before refitting.
The resistance will vary according the boiler temperature but should conform approximately to the table below:
Temperature °CResistance in kOhms
2022
309.4
407
507.3
604.7
703.8
802.8