Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
CH Demand
Attach temperature probes as indicated by the red arrows
Gas On
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow fan to run and boiler to fire and allow system to reach a reasonable operating temperature.
Measure the temperature of the flow and return pipes close to the primary heat exchanger.
Expected differential approx 11-20 °C
Note:
For clarity the test is shown with the fan and burner removed but the test is carried out with these in place.
Click on your observation:
1. DIFFERENTIAL OK NOISE DUE TO EXCESSIVE HEAT
2.DIFFERENTIAL NOT OK NOISE LOCAL BOILING
3.DIFFERENTIAL OK SYSTEM NOISE