Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Disconnect connector from X20 on the PCB
Measurement:
Measure resistance across the two green leads at the disconnected connector, and the approximate temperature at the sensors location.
The resistance will vary according the boiler temperature but should conform approximately to the table below at the appropriate temperature to ensure it is within range and in calibration:
The resistance will vary according the boiler temperature but should conform approximately to the table below at the appropriate temperature to ensure it is within range and in calibration:
| Temperature °C | Resistance in kOhms | 20 | 10 |
| 30 | 7.6 |
| 40 | 4.5 |
| 50 | 2.6 |
| 60 | 1.1 |
| 70 | 0.8 |

Isolate as per TOPs P4
and refit as necessary