Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to Resistance Set meter to measure resistance
Remove the two leads (blue) from the return sensor

Measurement:

Measure the resistance between the sensor terminals, also measure the approximate temperature at the sensor location.
The resistance will vary according the boiler temperature but should conform to the table below at the appropriate temperature to ensure it is within range and in calibration
Temperature °CResistance in kOhms
2010
30 6.6
405.8
503.1
602
701.5
801.1