Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Observation:
Remove and thoroughly inspect the spark electrode assembly and its ceramic for damage and good general condition.
Ensure the spark gap is 4 mm +/-0.5mm
Note:
Inspect the condition of any gaskets or seals disturbed during this test and renew if necessary.
Ensure the spark gap is 4 mm +/-0.5mm
Note:
Inspect the condition of any gaskets or seals disturbed during this test and renew if necessary.
Isolate as per TOPs P4
and refit as necessary