Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to DC Volts Set meter to measure DC Volts
DHW Demand
Remove control box cover if necessary
Gas On
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow fan to start.
After approximately 8 seconds measure voltage across the white wire on connector X36 and the neutral at the incoming mains terminal strip, with connector X36 attached to the PCB.
Expected voltage approximately 13 vdc
Note:
Voltage will only be present for approximately 1-3 seconds during the ignition phase, the appliance will try to ignite several times before going to lockout.