Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
Measure temp across cold mains inlet and DHW outlet using Performance Tester temp probes, as close to the secondary heat exchanger as possible
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow boiler to ignite and run on DHW.
Is the temperature rise approximately per the table?
Note: Flow rates lower than specified will result in a higher temperature rise and this must be taken into account when selecting the outcome of the test. To investigate a poor water flow rate from the tap CLICK HERE.