Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove electrical connector from diverter valve head
Measurement:
Observe the position of the spindle.
If the spindle is extended test between pins 2 and 3.
Expect approximately 9 Kohms.
If the spindle is retracted test between pins 1 and 2.
Expect approximately 9 Kohms.
If the spindle is not fully in one position test between pins 1 & 2 then pins 2 & 3.
Expect approximately 9 Kohms.
Note:
Pin numbers are printed or stamped on the diverter valve head itself.
If the spindle is extended test between pins 2 and 3.
Expect approximately 9 Kohms.
If the spindle is retracted test between pins 1 and 2.
Expect approximately 9 Kohms.
If the spindle is not fully in one position test between pins 1 & 2 then pins 2 & 3.
Expect approximately 9 Kohms.
Note:
Pin numbers are printed or stamped on the diverter valve head itself.

Isolate as per TOPs P4
and refit as necessary