Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove 8 way connector from PCB
Measurement:
Measure resistance across the two red wires on the 8 way PCB connector.
Note:
Boiler may go to overheat lockout if the thermistor resistance goes below approx. 700 Ohms.
Note:
Boiler may go to overheat lockout if the thermistor resistance goes below approx. 700 Ohms.

Isolate as per TOPs P4
and refit as necessary