Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4

Observation:

Check the appliance and system for any air and also that the system pressure is correctly set (1-1.5bar when cold).
Check the auto air vent is open and operating correctly.
Add a small amount of pressure via the filling loop and observe the gauge to see if it reflects the increase in system pressure.