As standard all 3 appliances in the range (80, 100 and 133 HE) are set to 23.9kW output for CH unless the red jumper is removed.
At the start of the XSol model both jumpers had to be removed which means the maximum CH output is set to 30kw for the Combi 100 and 133 but remains unchanged in the case of the Combi 80.
It is advisable to consider the original jumper setting if the customer had reported insufficient heat from the boiler and system as this could have been due to incorrectly set jumpers keeping the appliance at a lower CH output.
Ensure the jumper arrangement is appropriate for the appliance fitted / the system requirements.
For further information regarding jumper settings and the operation of the intelligent preheat click here.