Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
Attach a temperature clamp to the flow pipe as indicated by the red arrow
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow the burner to ignite and establish for DHW.
Turn the hot water tap OFF.
Monitor the temperature of the appliance and the radiators as the preheat operates.
The temperature of the appliance should reach approximately 60°C and then the burner should shut down. When the tap LED extinguishes the preheat cycle is complete (this can be up to 1 minute after the burner extinguished).
While the boiler completes preheat the radiators should not start to heat up.
Does the preheat operate correctly?