Set Appliance State:

Turn Hot Water Tap On
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow boiler to ignite and run on DHW.
With a flow rate as listed in the table below a temperature rise of approximately 35°C is expected.
ApplianceFlow Rate
80 HE10 l/min
100 HE12 l/min
133 HE16 l/min

Does the hot water operate satisfactorily and is the temperature rise as expected?
Note:
A lower flow rate will produce a greater temperature rise.
If you wish to investigate a poor DHW flow rate click HERE