Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach a temperature clamp to the flow pipe as indicated by the red arrow
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the boiler to run in central heating mode.
Monitor the temperature of the boiler as it operates.
It should heat until approximately 80°C (maximum temperature) then shut down or maintain temperature at this level without overheating.
Does the boiler behave as described?
Monitor the temperature of the boiler as it operates.
It should heat until approximately 80°C (maximum temperature) then shut down or maintain temperature at this level without overheating.
Does the boiler behave as described?