Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Gain access to PCB (use Insulation Mat as required)
Selector switch to DHW position
CH temperature selector to Min
DHW temperature selector to Max
Selector switch to DHW position
CH temperature selector to Min
DHW temperature selector to Max
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Test 1:
Measure the voltage at the purple connection to neutral.
Test 2:
Measure the voltage at the pink connection to neutral.
For both tests approximately 25 volts should be present
during the ignition process.
Measure the voltage at the purple connection to neutral.
Test 2:
Measure the voltage at the pink connection to neutral.
For both tests approximately 25 volts should be present
during the ignition process.

Isolate as per TOPs P4
and refit as necessary