Set Appliance State:

CH Demand
Isolate Mains Power to appliance as per TOPs P4
Attach two temperature clamps to the flow and return pipes from the primary heat exchanger as near as possible to the thermistors
Gas On
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow the appliance to run in CH mode for a few minutes.
Monitor the temperature differential while the appliance runs.
Expect a temperature differential of approximately 20°C or less.
Is the temperature differential as expected?