Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to DC Volts Set meter to measure DC Volts
Disconnect the 3 wire speed control from the pump assembly and make safe
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Reset appliance if required.
(press and hold the reset button for 4 seconds then release)
Allow the pump to run during the appliance self-check.
Measure the DC voltage between pin 20 of connector X2 and an earth (use the copper pipe to the gas valve as earth).
Expect approximately 16V DC or greater.
Is the voltage measured as expected?