Set Appliance State:
Turn Hot Water Tap On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow boiler to ignite and run on DHW.
Manufacturers specification is with a flow rate of 8.0 litres/min through the appliance, a temperature rise of approximately 42°C is expected.
Note:
A lower flow rate will produce a greater temperature rise.
If you wish to investigate a poor DHW flow rate click HERE
Manufacturers specification is with a flow rate of 8.0 litres/min through the appliance, a temperature rise of approximately 42°C is expected.
Note:
A lower flow rate will produce a greater temperature rise.
If you wish to investigate a poor DHW flow rate click HERE