Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to DC Volts Set meter to measure DC Volts
Turn Hot Water Tap On
Gain access to PCB (use Insulation Mat as required)
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Reset appliance if required (press reset button once and release).
Measure for DC voltage between pin 9 (blue) on connector X20
and the earth point on the boiler chassis.
When the fan starts, approximately 16 - 22 Vdc should be present for 4 seconds, this will then be present again after approximately 6 seconds. This will be repeated 5 times before lockout occurs, reset as required until test complete.
Note:
1. Ensure a good connection is made or misdiagnosis will occur.
2. Each pin on the PCB connector is numbered.