Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach temperature clamps to the flow and return pipes of
the primary heat exchanger (as indicated by the red arrows)
Note:
Ensure a good connection is made with the flow & return pipes
or misdiagnosis will occur
the primary heat exchanger (as indicated by the red arrows)
Note:
Ensure a good connection is made with the flow & return pipes
or misdiagnosis will occur
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Measure the temperature differential at the
time the system noise occurs.
Expect a temperature differential of approximately 22°C or less.
time the system noise occurs.
Expect a temperature differential of approximately 22°C or less.