Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Gain access to PCB (use Insulation Mat as required)
Ensure all external controls are calling
Ensure all external controls are calling
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure the AC voltage between the terminal marked RT at the connector for the incoming 240v external controls and the earth on the same connector.
Expect mains voltage.
Note:
If the appliance is fitted with 240v external controls the link present between the two terminals for 24v controls (marked RT on connector X100) should have been removed.
Expect mains voltage.
Note:
If the appliance is fitted with 240v external controls the link present between the two terminals for 24v controls (marked RT on connector X100) should have been removed.

Isolate as per TOPs P4
and refit as necessary