Set Appliance State:

Ensure NO demands
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Note:
Diagnostic code D.071 is set as default at 75°C
but it can be set between 40 - 80°C.
Click HERE for guidance on how to access the Diagnostic codes.
Alternatively refer to Adapt for guidance.
Once you navigate to D.071 the maximum heating flow temperature
value will be displayed underneath the Diagnostic code.
Is the value in Diagnostic code D.071 set at a sufficient temperature suitable for the customer’s requirements ?