Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
DHW Selector in Minimum (-) position
CH Selector in Maximum (+) position
ON/OFF Switch in ON position
DHW Selector in Minimum (-) position
CH Selector in Maximum (+) position
ON/OFF Switch in ON position
Boiler temperature must be at MAX for this test (75°C)
If necessary run CH till MAX temp reached
Disconnect connector X20 from the on the PCB
If necessary run CH till MAX temp reached
Disconnect connector X20 from the on the PCB
Measurement:
Measure resistance across connections 13 (black) and 12 (black) at the disconnected connector X20.
Expected resistance closed circuit zero resistance.
Expected resistance closed circuit zero resistance.

Isolate as per TOPs P4
and refit as necessary