Set Appliance State:
Mains Power Off
CH Demand
DHW Selector in Minimum (-) position
CH Selector in Maximum (+) position
ON/OFF Switch in ON position
DHW Selector in Minimum (-) position
CH Selector in Maximum (+) position
ON/OFF Switch in ON position
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Once appliance has completed its ignition sequence the boiler should run on low rate for approximately 45 seconds before ramping up.
Allow boiler to run CH up to temperature.
Does the fan speed reduce as the boiler temperature meets demand?
Notes:
If it is not possible to hear the fan speed reduce (e.g. in a noisy environment) the fan speed can be checked by viewing d.34 on the boiler display.
Click HERE for information on how to access d.34.
If boiler is already near temperature it will not ramp up.
Allow boiler to run CH up to temperature.
Does the fan speed reduce as the boiler temperature meets demand?
Notes:
If it is not possible to hear the fan speed reduce (e.g. in a noisy environment) the fan speed can be checked by viewing d.34 on the boiler display.
Click HERE for information on how to access d.34.
If boiler is already near temperature it will not ramp up.