Set Appliance State:
Turn Hot Water Tap On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow boiler to ignite and run on DHW.
With a flow rate as listed in the table below a temperature rise of approximately 42°C is expected.
Does the hot water operate satisfactorily and is the temperature rise as expected?
Note:
A lower flow rate will produce a greater temperature rise.
If you wish to investigate a poor DHW flow rate click HERE
With a flow rate as listed in the table below a temperature rise of approximately 42°C is expected.
| Appliance | Flow Rate |
| 824/2 E | 7.9 l/min | 828/2 E | 9.6 l/min | 835 E | 11.9 l/min |
Does the hot water operate satisfactorily and is the temperature rise as expected?
Note:
A lower flow rate will produce a greater temperature rise.
If you wish to investigate a poor DHW flow rate click HERE