Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to Resistance Set meter to measure resistance
CH Demand
Disconnect leads from the Air Pressure Switch and make safe
Attach the multimeter Probes to the Air Pressure Switch Terminals
ON/OFF Switch in OFF Position
CH Temp Selector in Maximum position
DHW Temp Selector in Minimum position
Mode Selector Switch in Heat and Hot water position
WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure
Mains Power On

Measurement:

If required reset boiler, turn CH / DHW control to reset position.
Multimeter should be reading open circuit.
While observing the multimeter, turn ON the boiler ON/OFF switch.
When the Fan runs and the Air Pressure Switch operates, the multimeter reading should change from open circuit to closed circuit.