Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Disconnect Sensor Lead
Measurement:
Measure resistance across the Sensor Terminal and a suitable earth point.
The resistance will vary according to the boiler temperature.
The hotter the boiler the lower the resistance.
It should conform to the table below:
The resistance will vary according to the boiler temperature.
The hotter the boiler the lower the resistance.
It should conform to the table below:
| Temperature °C | Resistance in kOhms |
| 30-40 | 2.1-1.3 |
| 40-50 | 1.3-0.8 |
| 50-60 | 0.8-0.6 |
| 60-70 | 0.6-0.4 |
| 70-80 | 0.4-0.3 |

Isolate as per TOPs P4
and refit as necessary