Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
ON/OFF switch in ON position
CH temp selector to MAX
Attach temperature clamps to primary flow and return pipes as indicated
CH temp selector to MAX
Attach temperature clamps to primary flow and return pipes as indicated
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow fan to run and boiler to ignite.
The boiler should run until it reaches temperature of approximately 82°C then modulate to maintain temperature or shut down.
The differential between the flow and return pipes should remain below 20°C.
Note:
You may wish to turn off some radiators to reduce the time taken for this test.
Differential may be higher on initial start-up.
The boiler should run until it reaches temperature of approximately 82°C then modulate to maintain temperature or shut down.
The differential between the flow and return pipes should remain below 20°C.
Note:
You may wish to turn off some radiators to reduce the time taken for this test.
Differential may be higher on initial start-up.