Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove the connector from the warm stat which is situated adjacent to the pump
Measurement:
Measure the resistance between the thermostat and a suitable earth point on the appliance (i.e. the pipe).
Measure the temperature of the flow pipe near the thermostat.
The resistance will vary according to the boiler temperature and it should conform to the table below.
Measure the temperature of the flow pipe near the thermostat.
The resistance will vary according to the boiler temperature and it should conform to the table below.
| Temperature °C | Resistance in kohms |
| 30 - 40 | 2.1 - 1.3 |
| 40 - 50 | 1.3 - 0.8 |
| 50 - 60 | 0.8 - 0.6 |
| 60 - 70 | 0.6 - 0.4 |
| 70 - 80 | 0.4 - 0.3 |

Isolate as per TOPs P4
and refit as necessary