Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to DC Volts Set meter to measure DC Volts
Remove the connector from the flow sensor and make safe
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Measure for DC volts between pin 3 on connector X2 and an earth connection (use the copper pipe to the gas valve as earth).
Expected voltage approximately 4.8 Vdc.
Is the voltage measured as expected?
Note.
Ensure a good connection is made or misdiagnosis may occur.