Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn hot water tap on fully
Attach temperature clamps to flow and return pipes
(as indicated by the red arrows)
Attach temperature clamps to flow and return pipes
(as indicated by the red arrows)
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the appliance to run in DHW mode for a few minutes.
Monitor the temperature differential as the appliance runs in DHW mode.
Expect a temperature differential of approximately 25°C or less.
Is the temperature differential as expected?
Monitor the temperature differential as the appliance runs in DHW mode.
Expect a temperature differential of approximately 25°C or less.
Is the temperature differential as expected?