Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Attach FGA to gas valve pressure outlet test point
Remove the left-hand side panel if required
Remove the left-hand side panel if required
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Reset appliance if required.
Allow the boiler to commence its ignition sequence.
With the fan running measure the fan pressure, the reading will be a negative pressure.
Expect a pressure of at least -1.5mb or greater (e.g. -3mb)
Allow the boiler to commence its ignition sequence.
With the fan running measure the fan pressure, the reading will be a negative pressure.
Expect a pressure of at least -1.5mb or greater (e.g. -3mb)
Isolate as per TOPs P4
and refit as necessary