Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to AC Volts Set meter to measure AC Volts
Turn Hot Water Tap On
Gain access to PCB (use Insulation Mat as required)
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow the boiler to run in DHW mode.
Measure the AC voltage between the L terminal at connector X15 on the PCB and the earth at the incoming mains connector.
Expect approximately 240 VAC.
Is the voltage measured as expected?