Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
CH temperature set to MAX
Attach temperature clamp to flow pipe of the primary heat exchanger
Attach temperature clamp to flow pipe of the primary heat exchanger
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow self-check to complete, the boiler to run for
central heating and the system to heat up.
Measure the temperature differential.
Expect a differential of approx. 25°C or less.
Note.
1. Ensure all radiators are open and system is balanced correctly
to provide correct test results.
2. Initial temperature differential may be greater than 30°C when
system is heated from cold.
central heating and the system to heat up.
Measure the temperature differential.
Expect a differential of approx. 25°C or less.
Note.
1. Ensure all radiators are open and system is balanced correctly
to provide correct test results.
2. Initial temperature differential may be greater than 30°C when
system is heated from cold.