Set Appliance State:
Set boiler to 100% output
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Check boiler gas rate with meter test dial and stop watch.
Gas rate shall be as per manufacturers specification for CH output (see notes).
Note:
1.The appliance must burn at 100% output throughout test. if the burner modulates results will be inaccurate.
2. Gas rate result must take into account any adjustments made to boiler output, due to flue types fitted to the boiler
(refer to manufacturers instructions).
3. If L.P.G appliance choose "Gas rate incorrect @ 100% output".
Gas rate shall be as per manufacturers specification for CH output (see notes).
Note:
1.The appliance must burn at 100% output throughout test. if the burner modulates results will be inaccurate.
2. Gas rate result must take into account any adjustments made to boiler output, due to flue types fitted to the boiler
(refer to manufacturers instructions).
3. If L.P.G appliance choose "Gas rate incorrect @ 100% output".