VITODENS 100-W COMPACT

WARNING - IMPORTA

Next: &1, *

INFORMATION CASE REMOVAL

Next: &3, !f2

OBSERVATION BOILER SELF CHECK

BOILER ON/OFF PUSHED IN, ON POSITION
ENSURE NO DEMANDS
LOCATE SYSTEM PUMP IF REQUIRED

Next: &71, ?4, ?6, ?8

TYPE OF DIAGNOSTIC PROCEDURE

PLEASE SELECT FROM O

Next: &950, !f74

OBSERVATION BURNER IGNITION & ESTABLISH

Next: &356, ?217, ?219, ?221

PRESSURE GAS INLET (BOILER IGNITED)

ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT

Next: &358, !f357

CH OPERATION

Next: &1180, ?361, ?363

DISPLAY CODE 30 38

NOT USED

Next: &nff, f528

DISPLAY CODE 60 68

GLOBAL PAGE

Next: &nff, f536

DISPLAY CODE A9

GLOBAL PAGE

Next: &nff, f1169

DISPLAY CODE B0 B8

NOT USED

Next: &nff, f562

DISPLAY CODE E5

NOT USED

Next: &nff, p1079

DISPLAY CODE F0

NOT USED

Next: &nff, f585

DISPLAY CODE F1

NOT USED

Next: &nff, f603

DISPLAY CODE F2

NOT USED

Next: &nff, f617

DISPLAY CODE F3

NOT USED

Next: &nff, f1113

DISPLAY CODE F8

NOT USED

Next: &nff, f654

DISPLAY CODE F9

NOT USED

Next: &nff, f668

DISPLAY CODE FD FF

NOT USED

Next: &nff, f678

FUSE FURTHER INVESTIGATION

NOT USED

Next: &nff, f686

OBSERVATION PUMP RUNS

LOCATE SYSTEM PUMP
ENSURE THAT SEVERAL RADIATORS ARE OPEN TO PROVIDE A CIRCULATION ROUTE

Next: &989, f951

OBSERVATION FAN RUNS

ENSURE BOILER IS COOL

Next: &216, f990

& DISPLAY CODE 10 18

GLOBAL PAGE

Next: &nff, f1119

& DISPLAY CODE 50 58

GLOBAL PAGE

Next: &nff, f1152

HOT WATER OPERATION

HW DEMAND

Next: &nff, ?1181, ?1183

FAN DOES NOT RUN

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN

Next: End

BURNER DOES NOT IGNITE

ELECTRODE - IGNITION AND IONIZATION

Next: End

BURNER DOES NOT ESTABLISH 2

ELECTRODE - IGNITION AND IONIZATION

Next: End

BURNER DOES NOT IGNITE 4

ELECTRODE - IGNITION AND IONIZATION

Next: End

BURNER DOES NOT ESTABLISH

ELECTRODE - IGNITION AND IONIZATION

Next: End

BOILER @ TEMP RADS COOL

MOTOR - PUMP

Next: End

BOIER TEMP LOW RADS COOL 2

SENSOR - TEMPERATURE

Next: End

SERVICE MODE 2

Z REDIRECT

Next: End

BOILER TEMP LOW RADS COOL

FLUE

Next: End

FAULT CODE E5

ELECTRODE - IGNITION AND IONIZATION

Next: End

FAULT CODE E5

CONTROL UNIT

Next: End

FAULT CODE F1

Next: End

FAULT CODE F1 2

CONTROL UNIT

Next: End

FAULT CODE F2 2

CONTROL UNIT

Next: End

FAULT CODE F2

Next: End

FAULT CODE F2 3

CONTROL UNIT

Next: End

FAULT CODE FD FF 2

ELECTRODE - IGNITION AND IONIZATION

Next: End

FAULT CODE F3

CONTROL UNIT

Next: End

FAULT CODE 10/18 2

CONTROL UNIT

Next: End

FAULT CODE 10/18

CONTROL UNIT

Next: End

FAULT CODE 50 58 2

CONTROL UNIT

Next: End

FAULT CODE 50 58

CONTROL UNIT

Next: End

FAULT CODE FD FF

ELECTRODE - IGNITION AND IONIZATION

Next: End

FAULT CODE FD FF

CONTROL UNIT

Next: End

FAULT CDOE A9

CONTROL UNIT

Next: End

FAULT CDOE A9 2

CONTROL UNIT

Next: End

FUSE FURTHER INVESTIGATION

MOTOR - PUMP

Next: End

FAN DOES NOT RUN

MOTOR - PUMP

Next: End

BOILER TEMP LOW RADS COOL

FAN - NRG

Next: End

FAULT CODE F2 2

THERMOCOUPLE

Next: End

FAULT CODE F2

Next: End

DISPLAY DOES NOT OPERATE

FUSE 2.5A (SLOW) 250V

Next: End

CASE REMOVAL

Z REDIRECT

Next: End

BURNER BAFFLES OR NOISY

CONDENSATE PIPEWORK

Next: End

BURNER BAFFLES OR NOISY

GAS INLET PRESSURE

Next: End

BURNER BAFFLES OR NOISY

FLUE

Next: End

BURNER DOES NOT IGNITE 2

CONDENSATE PIPEWORK

Next: End

BURNER DOES NOT ESTABLISH

GAS INLET PRESSURE

Next: End

BURNER DOES NOT IGNITE

CONDENSATE PIPEWORK

Next: End

BURNER DOES NOT IGNITE

GAS VALVE AND CONTROL UNIT

Next: End

BURNER DOES NOT IGNITE

FLUE

Next: End

BURNER DOES NOT IGNITE 3

GAS VALVE

Next: End

GAS INLET DHW DEMAMD

GAS INLET PRESSURE

Next: End

BOILER TEMP LOW RADS COOL

MOTOR - PUMP

Next: End

BOILER TEMP LOW RADS COOL

SENSOR - TEMPERATURE

Next: End

FAULT CODE 30

SENSOR - TEMPERATURE

Next: End

FAULT CODE 30

CONTROL UNIT

Next: End

FAULT CODE 51

SENSOR - TEMPERATURE

Next: End

FAULT CODE 51

CONTROL UNIT

Next: End

FAULT CODE 80

SENSOR - TEMPERATURE - FLUE GAS

Next: End

FAULT CODE B0 B8

CONTROL UNIT

Next: End

FAULT CODE F0

CONTROL UNIT

Next: End

FAULT CODE F1

SENSOR - TEMPERATURE - FLUE GAS

Next: End

FAULT CODE F1

CONTROL UNIT

Next: End

FAULT CODE F1

MOTOR - PUMP

Next: End

FAULT CODE F1

SENSOR - TEMPERATURE

Next: End

FAULT CODE F1

HEAT EXCHANGER

Next: End

FAULT CODE F2

MOTOR - PUMP

Next: End

FAULT CODE E3

SENSOR - TEMPERATURE

Next: End

FAULT CODE F2

SENSOR - TEMPERATURE

Next: End

FAULT CODE F8

GAS VALVE

Next: End

NO DISPLAY

FUSE (FUSED SPUR)

Next: End

FAULT CODE F8

ELECTRODE - IGNITION AND IONIZATION

Next: End

FAULT CODE F8

CONTROL UNIT

Next: End

FAULT CODE F9 FA FC 2

CONTROL UNIT

Next: End

FAULT CODE FD FF

EMC FIELD

Next: End

FUSE FURTHER INVESTIGATION

FAN - NRG

Next: End

FUSE FURTHER INVESTIGATION

GAS VALVE

Next: End

FAULT CODE F9

CABLE HARNESS - FAN

Next: End

FAULT CODE F9 FA FC

HARNESS

Next: End

FAULT CODE F9

CONTROL UNIT

Next: End

USER CONTROLS

Z REDIRECT

Next: End

TYPE OF DIAGNOSTIC PROCEDURE

Z REDIRECT

Next: End

FAULT CODE 2

Z REDIRECT

Next: End

BOILER RESET INFORMATION 2

Z REDIRECT

Next: End

SELF CHECK 2

CONTROL UNIT

Next: End

SELF CHECK

SENSOR - TEMPERATURE

Next: End

PUMP DOES NOT RUN

Next: End

CH DOES NOT RESPOND

INTERNAL TIMER/PROGRAMMER

Next: End

PUMP DOES NOT RUN

CONTROL UNIT

Next: End

FAN DOES NOT RUN

HARNESS

Next: End

FAN DOES NOT RUN 2

CONTROL UNIT

Next: End

BURNER DOES NOT IGNITE 4

GAS VALVE

Next: End

BURNER DOES NOT IGNITE 1

GAS VALVE

Next: End

BURNER BAFFLES OR NOISEY

GAS VALVE

Next: End

BURNER DOES NOT IGNITE

GAS VALVE

Next: End

BURNER DOES NOT IGNITE

BURNER GAUZE ASSEMBLY

Next: End

BURNER DOES NOT IGNITE

HEAT EXCHANGER

Next: End

BURNER DOES NOT IGNITE 2

ELECTRODE - IGNITION AND IONIZATION

Next: End

BURNER DOES NOT ESTABLISH

CONTROL UNIT

Next: End

BURNER DOES NOT ESTABLISH

BURNER GAUZE ASSEMBLY

Next: End

BURNER DOES NOT ESTABLISH

HEAT EXCHANGER

Next: End

BURNER DOES NOT IGNITE 3

ELECTRODE - IGNITION AND IONIZATION

Next: End

BURNER DOES NOT IGNITE 3

CONTROL UNIT

Next: End

BOILER TEMP LOW RADS COOL

CONTROL UNIT

Next: End

SERVICE MODE

Z REDIRECT

Next: End

BOILER TEMP LOW RADS COOL

EXTENSION - VENTURI

Next: End

BOILER TEMP LOW RADS COOL

GAS VALVE

Next: End

FAULT CODE E5

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE F1 2

MOTOR - PUMP

Next: End

FAULT CODE F1

PUMP WIRING

Next: End

FAULT CODE F2 2

MOTOR - PUMP

Next: End

FAULT CODE F2

PUMP WIRING

Next: End

FAULT CODE F2

FAULT CODE F2 - OVERHEAT

Next: End

FAULT CODE F3

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE 10 OR 18

OUTDOOR SENSOR

Next: End

FAULT CODE 10 OR 18

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE 10 OR 18 2

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE 50 58

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE 50 58 2

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE 50 58 2

CYLINDER DEMAND BOX

Next: End

FAULT CODE FD FF

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CDOE A9 2

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CDOE A9

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CDOE A9

OPEN THERM DEVICE

Next: End

FUSE FURTHER INVESTIGATION

PUMP WIRING

Next: End

HW OPERATION

Next: End

HW OPERATION

Next: End

FAN DOES NOT RUN

SWITCH-FLOW

Next: End

BOILER TEMP LOW RADS COOL

BURNER GAUZE ASSEMBLY

Next: End

BOILER TEMP LOW RADS COOL

HEAT EXCHANGER

Next: End

BOILER TEMP LOW RADS COOL 2

CONTROL UNIT

Next: End

FAULT CODE F2 4

CONTROL UNIT

Next: End

FAULT CODE F2

HARNESS

Next: End

NO DISPLAY

CONTROL UNIT

Next: End

FUSE FURTHER INVESTIGATION

Z REDIRECT

Next: End

BURNER BAFFLES OR NOISY

SIPHON

Next: End

BURNER BAFFLES OR NOISY

EXTENSION - VENTURI

Next: End

BURNER BAFFLES OR NOISY

GAS VALVE

Next: End

BURNER BAFFLES OR NOISY

BURNER GAUZE ASSEMBLY

Next: End

BURNER BAFFLES OR NOISY

HEAT EXCHANGER

Next: End

BURNER DOES NOT IGNITE 2

SIPHON

Next: End

BURNER DOES NOT IGNITE

SIPHON

Next: End

BURNER DOES NOT IGNITE

CONTROL UNIT

Next: End

BURNER DOES NOT IGNITE

CABLE GAS VALVE AND CONTROL UNIT

Next: End

BURNER DOES NOT IGNITE

GAS INLET PRESSURE

Next: End

BURNER DOES NOT IGNITE

CABLE HARNESS - GAS SOLENOID VALVE

Next: End

BURNER DOES NOT IGNITE

EXTENSION - VENTURI

Next: End

BURNER DOES NOT IGNITE 2

GAS VALVE

Next: End

BURNER DOES NOT IGNITE 2

BURNER GAUZE ASSEMBLY

Next: End

BURNER DOES NOT IGNITE 2

HEAT EXCHANGER

Next: End

BURNER DOES NOT ESTABLISH 2

CONTROL UNIT

Next: End

FAULT CODE 30

HARNESS

Next: End

FAULT CODE 30

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE 51

HARNESS

Next: End

FAULT CODE 51

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE B0

HARNESS

Next: End

FAULT CODE B0

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE F0

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

NO DISPLAY 2

CONTROL UNIT

Next: End

FAULT CODE F1

BOILER RESET - FAULT CODE F1

Next: End

NO DISPLAY

Next: End

FAULT CODE F2

THERMOCOUPLE

Next: End

FAULT CODE F2

CONTROL UNIT

Next: End

NO DISPLAY

Z REDIRECT

Next: End

FAULT CODE F8

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE F8 2

GAS VALVE

Next: End

FAULT CDOE F8

FAULT CODE RESET - RETEST BOILER OPERATION

Next: End

FAULT CODE F9 FA FC

FAN - NRG

Next: End

FUSE FURTHER INVESTIGATION

CONTROL UNIT - FUSE BLOWN

Next: End

FUSE FURTHER INVESTIGATION

CABLE HARNESS - FAN

Next: End

FUSE FURTHER INVESTIGATION 2

CABLE HARNESS - GAS SOLENOID VALVE

Next: End

FAULT CODE

Z REDIRECT

Next: End

BURNER DOES NOT IGNITE 2

EXTENSION - VENTURI

Next: End

SELF CHECK

Next: End

BOILER SELF CHECK

FROST PROTECTION NORMAL OPERATION

Next: End

SELF CHECK

CONTROL UNIT

Next: End

DISPLAY DOES NOT OPERATE 2

CONTROL UNIT

Next: End

PUMP DOES NOT RUN 2

CONTROL UNIT

Next: End

PUMP DOES NOT RUN 3

CONTROL UNIT

Next: End

PUMP DOES NOT RUN

MOTOR - PUMP

Next: End

PUMP DOES NOT RUN

PUMP WIRING

Next: End

BURNER RESTRICTED AND/OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

Next: !p1014

HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

Next: !p1016

ELECTRODE GAP TO BURNER SURFACE INCORRECT

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE

Next: !p1018

BURNER RESTRICTED AND/OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

Next: !p1025

HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

Next: !p1027

ELECTRODE GAP TO BURNER SURFACE INCORRECT

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE

Next: !p1029

HOW TO SET BOILER TO 100% OUTPUT

CHARACTERISTIC TEST FROM BOILER OUTPUT

Next: p1053

AIR INTAKE RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI

Next: !p1064

VENTURI RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI

Next: !p1066

RESISTANCE NOT AS EXPECTED

CHARACTERISTIC TEST FROM RESISTANCE OUTSIDE TEMPERATURE SENSOR AND HARNESS

Next: !p1122

NO OUTDOOR SENSOR INSTALLED

CHARACTERISTIC TEST FROM RESISTANCE OUTSIDE TEMPERATURE SENSOR AND HARNESS

Next: p1124

HW DEMAND NOT RECOGNISED

CHARACTERISTIC TEST FROM HOT WATER OPERATION

Next: !p1182

HW OPERATION UNSATISFACTORY

CHARACTERISTIC TEST FROM HOT WATER OPERATION

Next: !p1184

BURNER RESTRICTED AND/OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

Next: !p1192

HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

Next: !p1194

BURNER DOES NOT IGNITE

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p218

BURNER IGNITES BUT DOES NOT ESTABLISH

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p220

BURNER IGNITES BUT BAFFLES OR IS NOISY

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p222

AIR INTAKE RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI

Next: !p234

VENTURI RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI

Next: !p1006

BURNER RESTRICTED AND/OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

Next: !p239

HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

Next: !p241

NO PRESSURE DROP OBSERVED

CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP

Next: p279

PRESSURE DROPS BELOW 17.4MB N.G. / 25MB L.P.G.

CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP

Next: !p281

AIR INTAKE RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI

Next: !p291

VENTURI RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI

Next: !p1005

BURNER RESTRICTED AND/OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

Next: !p296

HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR DAMAGED

CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

Next: !p298

BOILER REACHES TEMPERATURE - RADIATORS DO NOT HEAT OR ONLY GET WARM

CHARACTERISTIC TEST FROM CH OPERATION

Next: p362

BOILER TEMPERATURE AND SYSTEM TEMPERATURE LOW - BOILER REMAINS LIT

CHARACTERISTIC TEST FROM CH OPERATION

Next: p438

PUMP RUNS CONTINUOUSLY OR BOILER ATTEMPTS TO FIRE AFTER SELF CHECK COMPLETE

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK

Next: p927

FAULT CODE DISPLAYED

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK

Next: p835

BOILER GOES TO FAULT CODE F2 BEFORE MAXIMUM FLOW TEMP REACHED

CHARACTERISTIC TEST FROM OBSERVATION CH - OVERHEAT OCCUR

Next: !p639

TEMPERATURE EXCEEDS MAXIMUM FLOW TEMPERATURE 80°C & CONTINUES TO FIRE

CHARACTERISTIC TEST FROM OBSERVATION CH - OVERHEAT OCCUR

Next: !p641

DELAY IN RETURNING TO STANDING PRESSURE

CHARACTERISTIC TEST FROM PRESSURE STANDING RETURN

Next: !p660

BOILER DOES NOT RESET - FAULT CODE REMAINS THE SAME

CHARACTERISTIC TEST FROM PRESSURE STANDING RETURN

Next: p662

DISPLAY DOES NOT OPERATE CORRECTLY

CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK

Next: p9

AIR INTAKE RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI

Next: !p860

VENTURI RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI

Next: !p1004

INSPECTION ELECTRODE

REMOVE ELECTRODE ASSEMBLY FROM BOILER

Next: !p1031, !f1032

VOLTAGE AT PUMP

EXPOSE WIRING CONNEC

Next: !p1086, f1087

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: !p1088, !f1089

VOLTAGE AT PUMP

EXPOSE WIRING CONNEC

Next: !p1091, f1092

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: !p1093, !f1094

VOLTAGE FAN ASSEMBLY (MAINS VOLTAGE)

{GAINPCBACS}

Next: !p937, f13

INSPECTION ELECTRODE

REMOVE ELECTRODE ASSEMBLY FROM BOILER

Next: p1114, !f1115

RESISTANCE OUTSIDE TEMPERATURE SENSOR AND HARNESS

IF INSTALLED DISCONN

Next: p1120, ?1121, ?1123

OBSERVATION CYLINDER DEMAND BOX INSTALLED

{GAINPCBACS}

Next: p1153, f1154

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1157, !f1158

DISCONNECT CYLINDER DEMAND BOX

DISCONNECT CYLINDER DEMAND BOX, CONNECTED TO 2X RED LEADS AS ILLUSTRATED & MAKE SAFE

Next: !p1162, !f1163

OBSERVATION OPEN THERM DEVICE INSTALLED

{GAINPCBACS}

Next: p1170, f1171

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1172, !f1173

DISCONNECT OPEN THERM DEVICE

DISCONNECT OPEN THERM DEVICE, CONNECTIONS ARE 1 & 2 OF TERMINAL BLOCK & MAKE SAFE

Next: !p1176, !f1177

RESISTANCE OVERHEAT STAT AND HARNESS

ENSURE BOILER IS COOL
REMOVE CONNECTOR X20 FROM PCB

Next: !p1198, f1199

RESISTANCE OVERHEAT STAT

REMOVE 1 X SPADE CONNECTOR FROM OVERHEAT STAT

Next: !p1200, !f1201

RESISTANCE FUSE F4 (PCB)

REMOVE PCB FUSE

Next: p60, f15

INSPECTION CONDENSATE PIPE

Next: !p225, !f226

INSPECTION CONDENSATE PIPE

Next: !p244, !f245

INSPECTION CONDENSATE PIPE

Next: !p268, !f269

RESISTANCE GAS VALVE AND HARNESS

REMOVE CONNECTOR 35 FROM THE PCB

Next: !p272, f273

RESISTANCE GAS VALVE

REMOVE CONNECTOR FROM GAS VALVE

Next: !p274, !f275

RESISTANCE GAS VALVE

REMOVE CONNECTOR FROM GAS VALVE

Next: !p286, !f287

VOLTAGE AT SPARK GENERATOR - SPARK ELECTRODE DISCONNECTED

REMOVE SPARK ELECTRODE LEAD FROM SPARK GENERATOR, MAKE SAFE
ENSURE NO DEMANDS

Next: !p352, !f1034

RESISTANCE FLOW TEMPERATURE SENSOR & HARNESS

REMOVE CONNECTOR X20 FROM THE PCB

Next: p529, f530

RESISTANCE FLOW TEMPERATURE SENSOR

REMOVE CONNECTORS FROM FLOW SENSOR

Next: !p531, !f532

RESISTANCE RETURN TEMPERATURE SENSOR & HARNESS

REMOVE CONNECTOR X20 FROM THE PCB

Next: p537, f538

RESISTANCE RETURN TEMPERATURE SENSOR

DISCONNECT INLINE CONNECTOR TO RETURN SENSOR

Next: !p539, !f540

RESISTANCE FLUE TEMPERATURE SENSOR AND HARNESS

REMOVE CONNECTOR X20 FROM THE PCB

Next: p563, f564

RESISTANCE FLUE TEMPERATURE SENSOR

DISCONNECT FLUE SENSOR INLINE CONNECTOR

Next: !p565, !f566

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p586, !f587

RESISTANCE FLUE TEMPERATURE SENSOR

DISCONNECT FLUE SENSOR INLINE CONNECTOR

Next: p604, !f605

RESET APPLIANCE - FAULT CODE F2

ENSURE NO DEMANDS ARE PRESENT
ENSURE BOILER IS COOL

Next: p618, f1197

RESISTANCE FUSED SPUR

REMOVE FUSE FROM FUSED SPUR

Next: !p63, f64

INSTALLATION TIGHTNESS TEST

Next: p655, !f656

VOLTAGE FAN ASSEMBLY (MAINS VOLTAGE)

{GAINPCBACS}

Next: p669, !f670

RESISTANCE FAN AND HARNESS

REMOVE CONNECTOR 100 FROM THE PCB

Next: p687, f688

RESISTANCE FAN

REMOVE MAINS VOLTAGE CONNECTOR TO FAN ASSEMBLY

Next: !p757, !f690

RESISTANCE GAS VALVE (FUSE)

REMOVE CONNECTOR FROM GAS VALVE

Next: !p758, !f698

RESISTANCE PUMP (FUSE INVESTIGATION)

REMOVE WIRING CONNECTIONS AT PUMP

Next: !p1179, !f1178

DISCONNECT EXTERNAL CONTROLS

{GAINPCBACS}
DISCONNECT SWITCHED LIVE (PIN1) FROM TERMINAL BLOCK & MAKE SAFE
NO DEMANDS

Next: !p930, !f931

RESISTANCE FLOW TEMPERATURE SENSOR

REMOVE CONNECTORS FROM FLOW SENSOR

Next: !p934, !f935

VOLTAGE SWITCHED LIVE

{GAINPCBACS}

Next: p954, !f955

DISCONNECT INTERNAL PROGRAMMER

DISCONNECT INTERNAL

Next: !p958, !f959

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: !p962, !f963

RESISTANCE FLOW SWITCH

DISCONNECT INLINE CONNECTOR TO FLOW SWITCH

Next: p991, f995

INSPECTION ELECTRODE

REMOVE ELECTRODE ASSEMBLY FROM BOILER

Next: p1009, !f1010

INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE

REMOVE BURNER MODULE UNIT ASSEMBLY FROM BOILER

Next: !p1011, ?1013, ?1015, ?1017

INSPECTION ELECTRODE

REMOVE ELECTRODE ASSEMBLY FROM BOILER

Next: p1020, !f1021

INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE

REMOVE BURNER MODULE UNIT ASSEMBLY FROM BOILER

Next: !p1022, ?1024, ?1026, ?1028

PUMP TEST

Next: p1037, !f1038

INSPECTION SYSTEM BYPASS

Next: !p1039, !f1041

RESISTANCE RETURN TEMPERATURE SENSOR

DISCONNECT INLINE CONNECTOR TO RETURN SENSOR

Next: p1048, !f1047

BOILER OUTPUT

SET BOILER TO 100% OUTPUT

Next: !p1049, ?1050, ?1052

INSPECTION FLUE

Next: p1056, !f1057

SERVICE MODE

Next: !p1054, !f1055

INSPECTION AIR INTAKE AND VENTURI

REMOVE AIR INTAKE MANIFOLD

Next: p1189, ?1063, ?1065

INSPECTION ELECTRODE

REMOVE ELECTRODE ASSEMBLY FROM BOILER

Next: p1080, !f1081

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1082, !f1083

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1116, !f1117

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1127, !f1128

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1125, !f1126

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1155, f1156

INSPECTION ELECTRODE

REMOVE ELECTRODE ASSEMBLY FROM BOILER

Next: p1165, !f1166

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1167, !f1168

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1174, f1175

PUMP TEST

Next: !p1186, !f1187

INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

REMOVE BURNER MODULE UNIT ASSEMBLY FROM BOILER

Next: p1190, ?1191, ?1193

INSPECTION FAN - INTERNAL

REMOVE BURNER ASSEMBLY FROM BOILER
SEPARATE FAN ASSEMBLY FROM BURNER ASSEMBLY

Next: !p1195, !f1196

INSPECTION SYSTEM BYPASS

Next: p630, !f1225

INSPECTION CONDENSATE SYPHON

GAIN ACCESS TO CONDENSATE SYPHON

Next: p266, f267

INSPECTION CONDENSATE SYPHON

GAIN ACCESS TO CONDENSATE SYPHON

Next: p242, f243

INSPECTION CONDENSATE SYPHON

GAIN ACCESS TO CONDENSATE SYPHON

Next: p223, f224

PRESSURE GAS INLET

ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT

Next: p227, !f228

INSPECTION FLUE

Next: p229, !f230

INSPECTION AIR INTAKE AND VENTURI

REMOVE AIR INTAKE MANIFOLD

Next: p231, ?233, ?235

INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

REMOVE BURNER MODULE UNIT ASSEMBLY FROM BOILER

Next: !p237, ?238, ?240

PRESSURE GAS INLET

ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT

Next: p246, !f247

VOLTAGE RECTIFICATION AT SPARK GENERATOR (NO DEMAND)

{GAINPCBACS}
ENSURE NO DEMANDS

Next: p1019, f351

VOLTAGE GAS VALVE AT PCB

{GAINPCBACS}

Next: p270, f271

PRESSURE GAS INLET DROP

ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT

Next: p276, ?278, ?280

OBSERVATION SPARKING OCCURS

REMOVE ELECTRODE LEA

Next: p845, f1030

INSPECTION FLUE

Next: p282, !f283

RESISTANCE GAS VALVE AND HARNESS

REMOVE CONNECTOR 35 FROM THE PCB

Next: p284, f285

INSPECTION AIR INTAKE AND VENTURI

REMOVE AIR INTAKE MANIFOLD

Next: p288, ?290, ?292

INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS

REMOVE BURNER MODULE UNIT ASSEMBLY FROM BOILER

Next: !p294, ?295, ?297

PUMP TEST

Next: p441, !f442

RESISTANCE FLOW TEMPERATURE SENSOR

REMOVE CONNECTORS FROM FLOW SENSOR

Next: p1043, !f444

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p533, !f534

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p541, !f542

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p567, !f569

VOLTAGE MAINS INPUT PCB

{GAINPCBACS}

Next: !p61, f62

RESET APPLIANCE - FAULT CODE F1

ENSURE NO DEMANDS ARE PRESENT
ENSURE BOILER IS COOL

Next: p606, !f607

PUMP TEST

Next: p610, !f611

RESISTANCE FLOW TEMPERATURE SENSOR

REMOVE CONNECTORS FROM FLOW SENSOR

Next: p612, !f613

OBSERVATION FLUE GAS TEMPERATURE

INSERT TEMPERATURE PROBE INTO FLUE GAS TEST POINT

Next: !p614, !f615

OBSERVATION PUMP RUNS

LOCATE SYSTEM PUMP
ENSURE THAT SEVERAL RADIATORS ARE OPEN TO PROVIDE A CIRCULATION ROUTE

Next: p624, f1090

PUMP TEST

Next: p1202, !f631

RESISTANCE FLOW TEMPERATURE SENSOR

REMOVE CONNECTORS FROM FLOW SENSOR

Next: p632, !f646

RESISTANCE RETURN TEMPERATURE SENSOR

DISCONNECT INLINE CONNECTOR TO RETURN SENSOR

Next: p634, !f635

OBSERVATION CH - OVERHEAT OCCUR

Next: p636, ?638, ?640

OBSERVATION PUMP OVERRUN

Next: !p1101, !f1102

PRESSURE STANDING RETURN

ATTACH U-GAUGE TO IN

Next: !p657, ?659, ?661

INSPECTION ELECTRODE

REMOVE ELECTRODE ASSEMBLY FROM BOILER

Next: p663, !f664

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p665, !f666

VOLTAGE FAN CONTROL

REMOVE 1 CONNECTOR F

Next: p671, !f708

RESISTANCE FAN CONTROL HARNESS

REMOVE FAN CONTROL CONNECTOR FROM FAN ASSEMBLY

Next: p673, !f707

RESISTANCE POWER CABLE FAN ASSEMBLY

REMOVE FAN POWER CONNECTOR TO FAN ASSEMBLY

Next: !p675, !f705

RESISTANCE PUMP AND HARNESS

REMOVE CONNECTOR 20 FROM THE PCB

Next: p691, f897

RESISTANCE GAS VALVE AND HARNESS (FUSE)

REMOVE CONNECTOR 35 FROM THE PCB

Next: !p710, f696

BOILER RESET INFORMATION

Next: p838, !f841

FAULT CODES

Next: !p839, !f840

INSPECTION AIR INTAKE AND VENTURI

REMOVE AIR INTAKE MANIFOLD

Next: p1008, ?859, ?861

OBSERVATION PUMP RUNS

LOCATE SYSTEM PUMP
ENSURE THAT SEVERAL RADIATORS ARE OPEN TO PROVIDE A CIRCULATION ROUTE

Next: p608, f1085

OBSERVATION FAN RUNS (NO DISPLAY)

REMOVE 1 CONNECTOR FROM OVERHEAT STAT AND MAKE SAFE

Next: !p1218, f11

TEMPERATURE FLOW PIPE (FROST PROTECTION)

ATTACH FGA TEMPERATURE SENSOR TO PRIMARY HEAT EXCHANGER FLOW CONNECTION

Next: !p932, f933

VOLTAGE AT PUMP

EXPOSE WIRING CONNEC

Next: !p960, f961

RESISTANCE FLOW SWITCH HARNESS

DISCONNECT INLINE CONNECTOR TO FLOW SWITCH

Next: p999, !f994

RESISTANCE FLOW TEMPERATURE SENSOR

REMOVE CONNECTORS FROM FLOW SENSOR

Next: !p1000, !f1001

System Information

  • Total Tests: 375
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control