Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
CH Demand
Refit combustion chamber if this has been removed
Place FGA probe in air inlet test point (below flue gas sample point)
ensure it is fitted securely to prevent any release of flue gases
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Reset appliance as necessary.
Allow burner to ignite and establish.
Set boiler to maximum output.
CLICK HERE FOR GUIDE
Allow FGA readings to stabilise and check that:
  • O₂ levels are equal or greater than 20.6%
  • CO₂ levels are less than 0.2%
    All FGA's supplied by British Gas are capable of measuring O₂.
    Please refer to performance tester instructions for information.