Set Appliance State:

Gas Off
Isolate Mains Power to appliance as per TOPs P4
CH Demand
Attach pressure gauge to the inlet pressure test point
Gas On
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Reset boiler if required.
Allow the fan to run, the ignition sequence to commence and the burner to ignite.
Does the pressure gauge show an inlet pressure of 14 mb or greater throughout the operation?
Note:
1. The manufacturer states the boiler range is able to deliver its full output
at inlet pressures as low as 14mb, however please refer to British Gas Technical
Operational Procedures for further guidance regarding gas inlet working pressures.
2. When "U" gauge is removed test point should be tightened and checked for gas tightness.