Set Appliance State:
Ensure NO demands
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Test 1:
Does the display illuminate?
(if it does not, press the reset button once briefly)
Test 2:
Reset the appliance.
(press and hold the reset button for 4 seconds then release)
After the appliance has reset the display should be illuminated with no fault code and a steady display of the current system pressure (as shown in the example - normal display)
Is the display as described above?
If "communication error" or "spare part invalid" is displayed click here.
Does the display illuminate?
(if it does not, press the reset button once briefly)
Test 2:
Reset the appliance.
(press and hold the reset button for 4 seconds then release)
After the appliance has reset the display should be illuminated with no fault code and a steady display of the current system pressure (as shown in the example - normal display)
Is the display as described above?
If "communication error" or "spare part invalid" is displayed click here.