Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
CH Demand
Attach temperature clamp to boiler flow pipe
CH Temperature Control to MAX
Selector switch in CH & HW mode
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Monitor the flow temperature as the boiler operates for CH.
Does the boiler go to fault code before reaching temperature or does it continue to fire past its maximum flow temperature?
Note:
If the fault is intermittent and does not reoccur (i.e. boiler reaches temperature and shuts down correctly) either repeat the test or click HERE to continue diagnosis through the full model.