Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to AC Volts Set meter to measure AC Volts
CH Demand
Gain access to PCB (use Insulation Mat as required)
Selector switch in CH & HW mode
Ensure no DHW demand
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow boiler to carry out ignition sequence and burner to ignite.
Approximately 5 seconds after the burner establishes measure the voltage between pin 5 (blue) and
pin 6 (black) wires of X3 on the main PCB.
Mains voltage should be present.