Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to DC Volts Set meter to measure DC Volts
CH Demand
Gain access to PCB (use Insulation Mat as required)
Selector switch in CH & HW mode
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Measure the voltage between pin 4 (light blue) at connector X401 at the PCB to a suitable earth point.
Voltage should start at approximately 6V DC, ramp up to 18V then drop back to 6V and repeat.