Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Hinge down the PCB housing
Reconnect fan connector at the fan if you have not already done so
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow fan to start to run.
Measure for DC volts across the green wire of
illustrated connector to a suitable neutral.
Expected voltage approx. 8V DC.
Measure for DC volts across the green wire of
illustrated connector to a suitable neutral.
Expected voltage approx. 8V DC.

Isolate as per TOPs P4
and refit as necessary